1600KVA dry type transformer

Date of issue: 2020/9/11 16:10:13 Source: http://perryswenson.com Click: zero

1600KVA dry-type transformer is suitable for some special occasions that need to change from 27.5kV grid voltage to 400V directly. Compared with 6-10KV distribution transformer, 1600KVA dry-type transformer has higher requirements for product manufacturing. Therefore, in the manufacturing process, the special transformer partial discharge control technology and internal stress control technology are used to control the internal insulation of the transformer in an ideal state, so as to ensure the key performance of the transformer. 1600KVA dry-type transformer is suitable for high-rise buildings, commercial centers, airports, tunnels, chemical plants, nuclear power plants, ships and other important or special environmental places.

香蕉视频下载app污ios
 1600KVA dry type transformer

Operating environment and conditions of 1600KVA dry type transformer:

1. Applicable altitude: ≤ 5000m.

2. Ambient temperature: - 15 ℃ ~ + 45 ℃.

3. Relative humidity: ≤ 90%.

4. The installation site shall be free of gas, steam, chemical deposition, dirt, conductive dust and other explosive, flammable and corrosive substances that seriously affect the insulation strength of the transformer.

5. Those that do not meet the above conditions shall be determined through consultation with us.

According to the user's requirements, 6.

The safe operation and service life of 1600KVA dry-type transformer largely depends on the safety and reliability of transformer winding insulation. It is one of the main reasons that the transformer can't work normally when the winding temperature exceeds the insulation withstand temperature. It is very important to monitor and alarm the operating temperature of the transformer. This paper introduces the GTB series temperature control system.

(1) automatic control of fan: temperature signal is measured by PT100 thermistor embedded in hot place of low-voltage winding. When the winding temperature reaches 110 ℃, the system will start the fan cooling automatically; when the winding temperature is lower than 90 ℃, the system will stop the fan automatically.

(2) overtemperature alarm and trip: temperature signal of winding or core is collected by PTC non-linear thermistor in embedded low-voltage winding. When the temperature of the transformer winding continues to rise, if it reaches 155 ℃, the system will output the over temperature alarm signal; if the temperature continues to rise to 170 ℃, the transformer can no longer continue to operate, so it is necessary to send the overtemperature trip signal to the secondary protection circuit to make the transformer trip quickly.

(3) temperature display system: the temperature change value is measured by PT100 thermistor embedded in the low-voltage winding, and the temperature of each phase winding can be directly displayed (three-phase inspection and value display, and historical temperature can be recorded). The temperature can be output in 4-20mA analog quantity. If it needs to be transmitted to a remote computer (the distance can be up to 1200m), a computer interface can be added, and one transmitter can be used to monitor more than 31 Transformers. The overtemperature alarm and trip of the system can also be activated by PT100 thermistor signal, which further improves the reliability of temperature control protection system.

1600KVA dry-type transformer is widely used in local lighting, high-rise buildings, airports, docks, CNC mechanical equipment and other places. Simply speaking, dry-type transformer refers to the transformer whose core and winding are not immersed in insulating oil. The cooling methods are divided into natural air cooling (an) and forced air cooling (AF). Under natural air cooling, the transformer can operate continuously for a long time under rated capacity. When forced air cooling, the output capacity of the transformer can be increased by 50%. It is suitable for intermittent overload operation or emergency overload operation; due to the large increase of load loss and impedance voltage during overload, it is in non economic operation state, so it should not be in continuous overload operation for a long time. Dry type transformer is mainly divided into open type, closed type and pouring type. Different types of 800kVA dry-type transformers have different prices.